Product photo
Modular UPS 200KVA-300KVA
HQ-M series modular UPS · online double conversion · scalable configuration for medium and large data rooms.
Models: HQ-M200 / HQ-M300
Rated capacity
200–300 kVA
System efficiency
96.5% (double conversion mode)
Output power factor
PF = 1
Display
10.4" touch screen + LED
| Parameter | Value |
|---|---|
| Model | HQ-M200 / HQ-M300 |
| Rated capacity | 200 kVA / 300 kVA |
| Power module quantity | 4+1 (200kVA) · 6+1 / 5+2 (300kVA) |
| Input wiring method | 3 Phase + N + PE |
| Input rated voltage | 380/400/415 VAC (line-line) |
| Input rated frequency | 50/60 Hz |
| Input voltage range | 304–478 VAC (line-line) full load; 304–228 VAC (line-line) load derating linearly from 100% to 80% |
| Input frequency range | 40–70 Hz |
| Input power factor | > 0.99 |
| THDi | < 3% (linear full load) · < 5% (non-linear full load) |
| Bypass rated voltage | 380/400/415 VAC (line voltage) |
| Bypass voltage range | Factory setting -20% ~ +15%; settable upper: +10%, +15%, +20%; settable lower: -10%, -20%, -30%, -40% |
| Bypass frequency range | Settable ±0.5 Hz, ±1 Hz, ±2 Hz, ±3 Hz, ±10% (default) |
| Bypass overload capacity | 110% for long run; >150% for 200 ms |
| Battery voltage | ±240 VDC (360–528 VDC; 30–44 units settable; default 40 units) |
| Output rated voltage | 380/400/415 VAC (line-line) |
| Output rated frequency | 50/60 Hz |
| Output power factor | 1 |
| Voltage accuracy | ≤ ±1.0% (balanced load) · ≤ ±5.0% (unbalanced load) |
| Frequency accuracy | 50/60 Hz ± 0.01% |
| Frequency tracking range | Settable ±0.5 Hz ~ ±5 Hz (factory setting: ±3 Hz) |
| THDu | ≤ 2% (100% linear load) · ≤ 4% (nonlinear load) |
| Three-phase phase accuracy | 120° ± 1° |
| Crest factor | 3:1 |
| Overload | <105% long run; <110% 60 mins; 110–125% 10 mins; >125–150% 1 min; >150% 200 ms |
| Protection class | IP20 |
| Standard | IEC62040-1-1; IEC62040-2; IEC62040-3 |
| Optional | SNMP card, parallel components, lightning protection components, dust-proof net, LBS, dry contact card |
| Working condition | Temperature: 0–40°C · Humidity: 0–95% (no condensation) |
| Noise | < 70 dB @ 1 meter |
| Altitude | <1000 m no derating; >1000 m derating 1% per each 100 m |
| Cabinet type | 5 (HQ-M200) · 7 (HQ-M300) |
| System size (W×D×H) | 600 × 850 × 2000 mm (HQ-M200) · 600 × 1100 × 2000 mm (HQ-M300) |
| Module size (W×D×H) | 440 × 720 × 130 mm (3U) |
| System weight | 190 kg (HQ-M200) · 286.5 kg (HQ-M300) |
| Minimum order | 60 |